• PD IEC/TS 62735-1:2015

    Current The latest, up-to-date edition.

    Direct current (DC) plugs and socket-outlets for information and communication technology (ICT) equipment installed in data centres and telecom central offices Plug and socket-outlet system for 2,6 kW

    Available format(s):  Hardcopy, PDF

    Language(s):  English

    Published date:  30-09-2015

    Publisher:  British Standards Institution

    Add To Cart

    Scope - (Show below) - (Hide below)

    This part of IEC62735, which is a Technical Specification, applies to plugs and fixed socket-outlets for class I equipment with two active contacts plus an earthing contact, a rated power of 2,6kW and a rated voltage range from 294V to 400V d.c. They are intended to power d.c. information and communication technology equipment only, products according to IEC60950.

    The accessories according to this part of IEC62735 are intended to be used by ordinary persons in data centres only where the value of the d.c. voltage distribution system is defined as follows:

    • 380V with a tolerance of±20V for installations with no backup battery or with a voltage regulation system;

    • 380V with a voltage range of 294V to 400V for installations with a backup battery where voltage regulation is not guaranteed;

    • the voltage value between each live conductor and earth does not exceed 200V d.c. during normal operation;

    • there are two abnormal voltage ranges (duration below 10min):

      • 260V up to 294V, and

      • above 400V to 410V.

    The maximum current of the plug and the socket-outlet is

    • 6,5A when the voltage between live contacts is 400V d.c.,

    • 8,8A when the voltage between live contacts is 294V d.c.

    and can rise up to 10A when the voltage between live contacts decreases to 260V d.c. for 10min maximum.

    The voltage between live conductors can fall down to 260V d.c. when the voltage discharge value of the battery reaches the disconnecting level. The consequence is that the current increases accordingly.

    The accessories according to this part of IEC62735 do not require maintenance.

    Plugs and socket-outlets covered by this part of IEC62735 are intended for use in circuits where

    • basic protection,

    • an overcurrent protection (of 8,8A or less for each socket-outlet or multiple socket-outlet),

    • the fault protection (indirect contact protection), and

    • additional protection

    are already assured.

    This part of IEC62735 does not cover requirements for flush mounting boxes: however, it covers only those requirements for surface-type mounting boxes which are necessary for the tests on the socket-outlet.

    NOTE1 General requirements for mounting boxes are given in IEC60670.

    This part of IEC62735 also applies to

    • plugs incorporated in cord sets,

    • plugs and socket-outlets incorporated in cord extension sets for data centres to be fixed to a wall or a rack,

    • the cord extension set and multiple socket-outlets for data centres intended to be fixed to a wall or a rack, and

    • socket-outlets which are a component of an assembly,

    unless otherwise stated in the standard for the relevant assembly.

    This part of IEC62735 does not apply to

    • single or multiple portable socket-outlets not fixed to a wall or a rack;

    • plugs, socket-outlets and couplers for industrial purposes;

    • plugs, socket-outlets and vehicle couplers for electric vehicles according to the IEC61851 and IEC62196 series;

    • plugs and socket-outlets for household;

    • appliance couplers;

    • plugs, fixed and portable socket-outlets for extra-low voltage (ELV);

      NOTE2 ELV values are specified in IEC60364-4-41.

    • fixed socket-outlets combined with fuses, automatic switches, etc.

    Socket-outlets with pilot lights are allowed provided that pilot lights comply with the relevant standard, if any.

    Plugs and socket-outlets complying with this part of IEC62735 are only suitable for use at ambient temperatures not normally exceeding+40°C, but their average over a period of 24h does not exceed+35°C, with a lower limit of the ambient air temperature of−5°C.

    Socket-outlets complying with this part of IEC62735 are only suitable for incorporation or mounting in equipment in such a way and in such a place that it is unlikely that the surrounding temperature exceeds 35°C.

    General Product Information - (Show below) - (Hide below)

    Committee PEL/23
    Document Type Standard
    Publisher British Standards Institution
    Status Current

    Standards Referencing This Book - (Show below) - (Hide below)

    IEC 60512-12-1:2006 Connectors for electronic equipment - Tests and measurements - Part 12-1: Soldering tests - Test 12a: Solderability, wetting, solder bath method
    IEC 60512-12-2:2006 Connectors for electronic equipment - Tests and measurements - Part 12-2: Soldering tests - Test 12b: Solderability, wetting, soldering iron method
    IEC 60050-151:2001 International Electrotechnical Vocabulary (IEV) - Part 151: Electrical and magnetic devices
    IEC 61210:2010 Connecting devices - Flat quick-connect terminations for electrical copper conductors - Safety requirements
    IEC 60695-2-11:2014 Fire hazard testing - Part 2-11: Glowing/hot-wire based test methods - Glow-wire flammability test method for end-products (GWEPT)
    IEC 60068-2-31:2008 Environmental testing - Part 2-31: Tests - Test Ec: Rough handling shocks, primarily for equipment-type specimens
    ISO 1456:2009 Metallic and other inorganic coatings — Electrodeposited coatings of nickel, nickel plus chromium, copper plus nickel and of copper plus nickel plus chromium
    ISO/IEC Guide 51:2014 Safety aspects Guidelines for their inclusion in standards
    IEC 60529:1989+AMD1:1999+AMD2:2013 CSV Degrees of protection provided by enclosures (IP Code)
    IEC 60423:2007 Conduit systems for cable management - Outside diameters of conduits for electrical installations and threads for conduits and fittings
    IEC 60352-2:2006+AMD1:2013 CSV Solderless connections - Part 2: Crimped connections - Generalrequirements, test methods and practical guidance
    IEC 61032:1997 Protection of persons and equipment by enclosures - Probes for verification
    IEC 60068-2-30:2005 Environmental testing - Part 2-30: Tests - Test Db: Damp heat, cyclic (12 h + 12 h cycle)