ASTM F 855 : 2014

Superseded

Superseded

A superseded Standard is one, which is fully replaced by another Standard, which is a new edition of the same Standard.

View Superseded by

Standard Specifications for Temporary Protective Grounds to Be Used on De-energized Electric Power Lines and Equipment

Available format(s)

Hardcopy , PDF

Superseded date

20-11-2014

Superseded by

ASTM F 855 : 2015

Language(s)

English

Published date

01-10-2014

€74.48
Excluding VAT

Committee
F 18
DocumentType
Standard
Pages
20
PublisherName
American Society for Testing and Materials
Status
Superseded
SupersededBy
Supersedes

1.1These specifications cover the equipment making up the temporary grounding system used on de-energized electric power lines, electric supply stations, and equipment.

1.2It is common practice for the users of protective grounding equipment to prepare complete instructions and regulations to govern in detail the correct use and maintenance of such equipment.

1.3The uses and maintenance of this equipment are beyond the scope of these specifications.

1.4These specifications for a system of protective grounding utilizing copper cables are covered in four parts, as follows:

Sections

Clamps for Temporary Protective Grounds

4 – 16

Ferrules for Temporary Protective Grounds

17 – 30

Cables for Temporary Protective Grounds

31 – 39

Protective Grounds (Complete Assembly With Clamps, Ferrules,   and Cable)

40 – 52

1.5Each of the four parts is an entity of itself, but is listed as a part of the system for completeness and clarification.

1.6Currents presented in Table 1 are based upon cable melting times, as determined from equations by I. M. Onderdonk and are to used in situations involving an asymmetry value less than 20 % (X/R 1.8). See Appendix X3.

(A)Withstand and ultimate short circuit properties are based on performance with surges not exceeding 20 % asymmetry factor (see 9.1 and 12.3.4.2).
(B)Yield shall mean no permanent deformation such that the clamp cannot be reused throughout its entire range of application.
(C)Ultimate rating represents a symmetrical current which the assembly or individual components shall carry for the specified time.
(D)Ultimate values are based upon application of Onderdonk's equation to 98 % of nominal circular mil area allowed by Specifications B172 and B173.

1.6.1Currents presented in Table 2 are based upon the values from EPRI Project RP2446 Computer Program RTGC “A Desktop Computer Program for Calculating Rating of Temporary Grounding Cables” and are to be used in situations involving an asymmetry value greater then 20 % (X/R 1.8), see Appendix X4.

Note 1:The above current values are based on electromechanical test values.

Note 2:Assemblies that have been subjected to these shall not be re-used.

Note 3:For use with currents exceeding 20 % asymmetry factor.

Note 4:See X4.7.2 for additional information.

Note 5:Alternate testing circuits are available for laboratories that cannot achieve the above requirements. See Appendix X4 for details.

Note 1:Table 1 represents the clamp and assembly ratings that existed prior to this revision. Table 2 represents new ratings now required for high X/R situations.

1.6.2See Appendix X3 and Appendix X4 for a discussion of these topics.

1.7The values stated in Newton-Meter units are to be regarded as the standard. The values in parentheses are the inch-pound units.

1.8The following precautionary caveat pertains to the test method portions, Sections 12 and 25 of these specifications: This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.