EN50525-3-41 applies to non-sheathed single core cables insulated with halogen-free crosslinked compound and having low emission of smoke and corrosive gases when exposed to fire.
NOTE1 Low emission of smoke is checked in accordance with EN61034-2. Low emission of corrosive gases is checked as part of the check for absence of halogens (see AnnexB of EN50525-1).
The cables are of rated voltages U0/U up to and including 450/750V.
NOTE2 Cables rated 450/750V may be used at 600/1000V when this cable is used in fixed installations with mechanical protection, within switchgear and control gear - see HD 516.
The cables are intended for fixed wiring applications.
The maximum conductor operating temperature for each of the cables in this standard is 90°C.
NOTE3 HD 516 contains extensive guidance on the safe use of cables in this standard.
This EN50525-3-41 should be read in conjunction with EN50525-1, which specifies general requirements.