CAN/CSA-C50068-99 (R2016)
Current
The latest, up-to-date edition.
Wrought Steel Enclosures for Gas-Filled High-Voltage Switchgear and Controlgear (Adopted CENELEC Standard EN 50068:1991 including Amendment A1:1993, with Canadian deviations)
Hardcopy , PDF
English, French
01-01-1999
1 Introduction
2 Scope and field of application
3 Definitions
4 Materials
5 Design
6 Manufacture and workmanship
7 Inspection and testing
8 Pressure relief devices
9 Certification and marking
Annexes
A Welding procedure and welder performance tests
B Sample of record form
C National deviations
Applicable to fusion welded wrought steel enclosures pressurized with dry air, inert gases, for example, sulphur hexafluoride, carbon tetrafluoride, or nitrogen or a mixture of such gases, used in indoor or outdoor installations of high-voltage switchgear and controlgear, where the gas is used principally for its dielectric and/or arc-quenching properties, with rated voltages: (a) 1 kV and up to and including 52 kV and with gas-filled compartments with design pressure greater than 3 bar (gauge); and (b) 72.5 kV and above. Also covers pressurized components such as the centre chamber of live tank switchgear, gas-insulated current transformers, etc.
DocumentType |
Standard
|
Pages |
0
|
ProductNote |
Reconfirmed EN
|
PublisherName |
Canadian Standards Association
|
Status |
Current
|
Supersedes |
Scope and Field of Application 2.1 Type of Equipment This Standard applies to fusion welded wrought steel enclosures pressurized with dry air, inert gases, eg, sulphur hexafluoride, carbon tetrafluoride, or nitrogen or a mixture of such gases, used in indoor or outdoor installations of high-voltage switchgear and controlgear, where the gas is used principally for its dielectric and/or arc-quenching properties, with rated voltages. a)1 kV and up to and including 52 kV and with gas-filled compartments with design pressure greater than 3 bar (gauge); and b)72.5 kV and above. The enclosures comprise parts of electrical equipment not necessarily limited to the following examples: - Circuit-breakers - Switch-disconnectors - Disconnectors - Earthing switches - Current transformers - Voltage transformers - Surge arresters - Busbars and connections The scope also covers pressurized components such as the centre chamber of live tank switchgear, gas-insulated current transformers, etc. 2.2 Production The production of the enclosures shall be in accordance with document ed welding procedures which shall be carried out by well trained and supervised welding personnel. Where international standards (ISO or CEN) are not available national standards may be used. NOTE - The standard will be revised as soon as possible when ISO or CEN standards covering the various aspects are available. 2.3 Quality Assurance It is the intention of this standard that the switchgear manufacturer shall be responsible for achieving and maintaining a consistent and adequate quality of product. Sufficient examinations shall be made by the enclosure manufacturer to ensure that the materials, production and testing comply in all respects with the requirements of this standard and ISO 6213:1983. Inspection by user\'s inspectors shall not absolve the switchgear manufacturer from this responsibility to exercise such quality assurance procedures as to ensure that the requirements and intent of this standard are satisf ied. NOTE - The manufacturer should have a quality assurance program registered to the applicable ISO 9000 series standards.
Standards | Relationship |
EN 50068 : 1991 COR 2007 | Similar to |
Access your standards online with a subscription
Features
-
Simple online access to standards, technical information and regulations.
-
Critical updates of standards and customisable alerts and notifications.
-
Multi-user online standards collection: secure, flexible and cost effective.