PD IEC/TS 62735-1:2015
Current
The latest, up-to-date edition.
Direct current (DC) plugs and socket-outlets for information and communication technology (ICT) equipment installed in data centres and telecom central offices Plug and socket-outlet system for 2,6 kW
Hardcopy , PDF
English
30-09-2015
Committee |
PEL/23
|
DocumentType |
Standard
|
Pages |
126
|
PublisherName |
British Standards Institution
|
Status |
Current
|
This part of IEC62735, which is a Technical Specification, applies to plugs and fixed socket-outlets for class I equipment with two active contacts plus an earthing contact, a rated power of 2,6kW and a rated voltage range from 294V to 400V d.c. They are intended to power d.c. information and communication technology equipment only, products according to IEC60950.
The accessories according to this part of IEC62735 are intended to be used by ordinary persons in data centres only where the value of the d.c. voltage distribution system is defined as follows:
380V with a tolerance of±20V for installations with no backup battery or with a voltage regulation system;
380V with a voltage range of 294V to 400V for installations with a backup battery where voltage regulation is not guaranteed;
the voltage value between each live conductor and earth does not exceed 200V d.c. during normal operation;
there are two abnormal voltage ranges (duration below 10min):
260V up to 294V, and
above 400V to 410V.
The maximum current of the plug and the socket-outlet is
6,5A when the voltage between live contacts is 400V d.c.,
8,8A when the voltage between live contacts is 294V d.c.
and can rise up to 10A when the voltage between live contacts decreases to 260V d.c. for 10min maximum.
The voltage between live conductors can fall down to 260V d.c. when the voltage discharge value of the battery reaches the disconnecting level. The consequence is that the current increases accordingly.
The accessories according to this part of IEC62735 do not require maintenance.
Plugs and socket-outlets covered by this part of IEC62735 are intended for use in circuits where
basic protection,
an overcurrent protection (of 8,8A or less for each socket-outlet or multiple socket-outlet),
the fault protection (indirect contact protection), and
additional protection
are already assured.
This part of IEC62735 does not cover requirements for flush mounting boxes: however, it covers only those requirements for surface-type mounting boxes which are necessary for the tests on the socket-outlet.
NOTE1 General requirements for mounting boxes are given in IEC60670.
This part of IEC62735 also applies to
plugs incorporated in cord sets,
plugs and socket-outlets incorporated in cord extension sets for data centres to be fixed to a wall or a rack,
the cord extension set and multiple socket-outlets for data centres intended to be fixed to a wall or a rack, and
socket-outlets which are a component of an assembly,
unless otherwise stated in the standard for the relevant assembly.
This part of IEC62735 does not apply to
single or multiple portable socket-outlets not fixed to a wall or a rack;
plugs, socket-outlets and couplers for industrial purposes;
plugs, socket-outlets and vehicle couplers for electric vehicles according to the IEC61851 and IEC62196 series;
plugs and socket-outlets for household;
appliance couplers;
plugs, fixed and portable socket-outlets for extra-low voltage (ELV);
NOTE2 ELV values are specified in IEC60364-4-41.
fixed socket-outlets combined with fuses, automatic switches, etc.
Socket-outlets with pilot lights are allowed provided that pilot lights comply with the relevant standard, if any.
Plugs and socket-outlets complying with this part of IEC62735 are only suitable for use at ambient temperatures not normally exceeding+40°C, but their average over a period of 24h does not exceed+35°C, with a lower limit of the ambient air temperature of−5°C.
Socket-outlets complying with this part of IEC62735 are only suitable for incorporation or mounting in equipment in such a way and in such a place that it is unlikely that the surrounding temperature exceeds 35°C.
Standards | Relationship |
IEC TS 62735-1:2015 | Identical |
IEC 60512-12-1:2006 | Connectors for electronic equipment - Tests and measurements - Part 12-1: Soldering tests - Test 12a: Solderability, wetting, solder bath method |
IEC 60512-12-2:2006 | Connectors for electronic equipment - Tests and measurements - Part 12-2: Soldering tests - Test 12b: Solderability, wetting, soldering iron method |
IEC 60050-151:2001 | International Electrotechnical Vocabulary (IEV) - Part 151: Electrical and magnetic devices |
IEC 61210:2010 | Connecting devices - Flat quick-connect terminations for electrical copper conductors - Safety requirements |
IEC 60695-2-11:2014 | Fire hazard testing - Part 2-11: Glowing/hot-wire based test methods - Glow-wire flammability test method for end-products (GWEPT) |
IEC 60068-2-31:2008 | Environmental testing - Part 2-31: Tests - Test Ec: Rough handling shocks, primarily for equipment-type specimens |
ISO 1456:2009 | Metallic and other inorganic coatings — Electrodeposited coatings of nickel, nickel plus chromium, copper plus nickel and of copper plus nickel plus chromium |
ISO/IEC Guide 51:2014 | Safety aspects — Guidelines for their inclusion in standards |
IEC 60529:1989+AMD1:1999+AMD2:2013 CSV | Degrees of protection provided by enclosures (IP Code) |
IEC 60423:2007 | Conduit systems for cable management - Outside diameters of conduits for electrical installations and threads for conduits and fittings |
IEC 60352-2:2006+AMD1:2013 CSV | Solderless connections - Part 2: Crimped connections - Generalrequirements, test methods and practical guidance |
IEC 61032:1997 | Protection of persons and equipment by enclosures - Probes for verification |
IEC 60068-2-30:2005 | Environmental testing - Part 2-30: Tests - Test Db: Damp heat, cyclic (12 h + 12 h cycle) |
Access your standards online with a subscription
Features
-
Simple online access to standards, technical information and regulations.
-
Critical updates of standards and customisable alerts and notifications.
-
Multi-user online standards collection: secure, flexible and cost effective.