The latest, up-to-date edition.

Tests for electric cables under fire conditions - Circuit integrity - Part 1: Test method for fire with shock at a temperature of at least 830°C for cables of rated voltage up to and including 0,6/1,0 kV and with an overall diameter exceeding 20 mm

Available format(s)

Hardcopy , PDF

Language(s)

Spanish, Castilian, English

Published date

04-11-2020

€97.20
Excluding VAT

This part of IEC 60331 specifies the test method for cables which are required to maintain

circuit integrity when subject to fire and mechanical shock under specified conditions.

This document is applicable to cables of rated voltage not exceeding 600 V/1 000 V, including

those of rated voltage below 80 V, metallic data and telecom cables and optical fibre cables.

It is intended for use when testing cables of greater than 20 mm overall diameter.

Cables of smaller diameter are intended to be tested using the apparatus, procedure and

requirements of IEC 60331-2.

This document includes details for the specific point of failure, continuity checking

arrangement, test sample, test procedure and test report relevant to electric power and

control cables with rated voltage up to and including 600 V/1 000 V. Details for the specific

point of failure, continuity checking arrangement, test sample, test procedure and test report

relevant to metallic data and telecom cables and optical fibre cables are not given by

IEC 60331-1.

Although the scope is restricted to cables with rated voltage up to and including 0,6/1,0 kV,

the procedure can be used, with the agreement of the manufacturer and the purchaser, for

cables with rated voltage up to and including 1,8/3 (3,3) kV, provided that suitable fuses are

used.

Annex A provides the method of verification of the burner and control system used for the

test.

Requirements are stated for an identification that may optionally be marked on the cable to

signify compliance with this document.

CAUTION The test given in this standard may involve the use of dangerous voltages

and temperatures. Suitable precautions should be taken against the risk of shock,

burning, fire and explosion that may be involved, and against any noxious fumes that

may be produced.

Committee
CTN 211/SC 20
DocumentType
Standard
Pages
35
PublisherName
Asociación Española de Normalización
Status
Current

Standards Relationship
IEC 60331-1:2018 Identical
EN IEC 60331-1:2019 Identical

Access your standards online with a subscription

  • Simple online access to standards, technical information and regulations.

  • Critical updates of standards and customisable alerts and notifications.

  • Multi-user online standards collection: secure, flexible and cost effective.

€97.20
Excluding VAT