UNE-EN IEC 62271-202:2023
Current
The latest, up-to-date edition.
High-voltage switchgear and controlgear - Part 202: AC prefabricated substations for rated voltages above 1 kV and up to and including 52 kV
Hardcopy , PDF
English, Spanish, Castilian
25-10-2023
This part of IEC 62271 specifies the service conditions, rated characteristics, general structural
requirements and test methods of enclosed high-voltage prefabricated substations. These
prefabricated substations are cable-connected to AC high-voltage networks with highest
operating voltage up to and including 52 kV and power frequencies up to and including 60 Hz.
They can be manually operated from inside (walk-in type) or from outside (non-walk-in
type).They are designed for outdoor installation at locations with public accessibility and where
protection of personnel is provided.
These prefabricated substations can be situated at ground level or partially or completely below
ground level. The last are also called underground prefabricated substations.
In general, two types of prefabricated substations are considered in this standard:
" high-voltage switching prefabricated substations;
" high-voltage/low-voltage transformer prefabricated substations (step-up and step-down).
A high-voltage switching prefabricated substation comprises an enclosure containing in general
the following electrical components:
" high-voltage switchgear and controlgear;
" auxiliary equipment and circuits.
A high-voltage/low-voltage transformer prefabricated substation comprises an enclosure
containing in general the following electrical components:
" power transformers;
" high-voltage and low-voltage switchgear and controlgear;
" high-voltage and low-voltage interconnections;
" auxiliary equipment and circuits.
However, relevant provisions of this standard are applicable to designs where not all these
electrical components exist (for example, a prefabricated substation consisting of power
transformer and low-voltage switchgear and controlgear).
The listed electrical components of a high-voltage/low-voltage transformer prefabricated
substation can be incorporated in the prefabricated substation either as separate components
or as an assembly type CEADS according to IEC 62271-212.
This standard covers only designs using natural ventilation. However, relevant provisions of
this standard are applicable to designs using other means of ventilation except the rated power
of the prefabricated substation and associated class of enclosure (see 5.101), the continuous
current tests (see 7.5) and all temperature rise related requirements, which would require an
agreement between manufacturer and user.
NOTE IEC 61936-1 [1] provides general rules for the design and erection of high-voltage power installations. As
well, it specifies additional requirements for the external connections, erection and operation at the place of
installation of high-voltage prefabricated substations compliant with IEC 62271-202, which are regarded as a
| Committee |
CTN 207/SC 17AC-32A
|
| DocumentType |
Standard
|
| Pages |
131
|
| PublisherName |
Asociación Española de Normalización
|
| Status |
Current
|
| SupersededBy | |
| Supersedes |
| Standards | Relationship |
| EN IEC 62271-202:2022 | Identical |
| IEC 62271-202:2022/COR1:2023 | Identical |
| EN IEC 62271-202:2022/AC:2023-09 | Identical |
| IEC 62271-202:2022 | Identical |
Access your standards online with a subscription
-
Simple online access to standards, technical information and regulations.
-
Critical updates of standards and customisable alerts and notifications.
-
Multi-user online standards collection: secure, flexible and cost effective.