• AS 1668.1-1991

    Superseded A superseded Standard is one, which is fully replaced by another Standard, which is a new edition of the same Standard.

    The use of mechanical ventilation and air-conditioning in buildings - Fire and smoke control

    Available format(s):  Hardcopy, PDF 1 User, PDF 3 Users, PDF 5 Users, PDF 9 Users

    Superseded date:  24-06-2021

    Language(s):  English

    Published date:  01-01-1991

    Publisher:  Standards Australia

    Add To Cart

    Table of Contents - (Show below) - (Hide below)

    1 - AS 1668.1-1991 THE USE OF MECHANICAL VENTILATION AND AIR-CONDITIONING IN BUILDINGS - FIRE AND SMOKE CONTROL
    4 - PREFACE
    5 - CONTENTS
    7 - SECTION 1 GENERAL
    7 - 1.1 SCOPE
    7 - 1.2 REFERENCED DOCUMENTS
    7 - 1.3 DEFINITIONS
    7 - 1.3.1 Shall
    7 - 1.3.2 May
    7 - 1.3.3 Air
    8 - 1.3.4 Air-handling plant
    8 - 1.3.5 Air-handling system
    8 - 1.3.6 Air-pressurization system
    8 - 1.3.7 Approved and approval
    8 - 1.3.8 Central air-handl ing system
    8 - 1.3.9 Combustible
    8 - 1.3.10 Compartment
    8 - 1.3.11 Downstream
    8 - 1.3.12 Duct
    8 - 1.3.13 Economy cycle
    8 - 1.3.14 Fail-safe
    8 - 1.3.15 Fire alarm
    8 - 1.3.16 Fire damper
    8 - 1.3.17 Fire-isolated
    8 - 1.3.18 Fire-isolated escape route
    8 - 1.3.19 Fire resistance level (FRL)
    8 - 1.3.20 Fire-resisting
    8 - 1.3.21 Flexible connection
    8 - 1.3.22 Incinerette
    8 - 1.3.23 Individual air-handling system
    8 - 1.3.24 Kitchen exhaust hood
    8 - 1.3.25 Masonry
    8 - 1.3.26 Plenum
    8 - 1.3.27 Purging smoke control
    8 - 1.3.28 Regulatory authority
    9 - 1.3.29 Required
    9 - 1.3.30 Shaft
    9 - 1.3.31 Smoke spill
    9 - 1.3.32 Smoke-spill system
    9 - 1.3.33 Subduct
    9 - 1.3.34 Toilet exhaust system
    9 - 1.3.35 Upstream
    9 - 1.3.36 Zone smoke control
    10 - SECTION 2 GENERAL REQUIREMENTS
    10 - 2.1 SCOPE AND APPLICATION
    10 - 2.2 DUCTWORK
    10 - 2.2.1 Early fire-hazard properties
    10 - 2.2.2 Combustibility and temperature of fusion
    10 - 2.2.3 Fire resistance
    10 - 2.2.4 Duct installation, general
    10 - 2.2.5 Unencased insulation of ducts
    10 - 2.3 PLENUMS
    10 - 2.4 FLEXIBLE CONNECTIONS
    10 - 2.5 FIRE DAMPERS
    10 - 2.6 SPACING FROM FIRE DAMPERS
    10 - 2.7 AIR-HANDLING PLANT CASINGS
    10 - 2.8 AIR FILTERS
    10 - 2.8.1 Location of air filters in relation to openings
    11 - 2.8.2 Liquid adhesive coatings
    11 - 2.8.3 Screens for filters
    11 - 2.9 ELECTRIC HEATERS
    11 - 2.9.1 General
    11 - 2.9.2 Integrity
    11 - 2.9.3 Surface temperature
    11 - 2.9.4 Thermal insulation
    11 - 2.9.5 Interlocking of power supply
    11 - 2.9.6 High-temperature-limiting thermostat
    11 - 2.9.7 Air-supply-failure sensor
    11 - 2.10 ELECTRICAL INSTALLATION
    11 - 2.11 AIR-HANDLING SYSTEMS SHUTDOWN
    11 - 2.11.1 General
    11 - 2.11.2 Small/special purpose systems
    11 - 2.11.3 Central air-handling systems
    12 - SECTION 3 OPENINGS IN FIRE-RESISTING CONSTRUCTION
    12 - 3.1 APPLICATION
    12 - 3.2 GENERAL
    12 - 3.2.1 Performance requirements
    12 - 3.2.2 Packing
    12 - 3.3 OPENINGS IN WALLS
    12 - 3.4 OPENINGS IN FLOORS
    12 - 3.4.1 Shafts
    12 - 3.4.2 Fire dampers
    12 - 3.5 FIRE-RESISTANT FLOOR/CEILING AND ROOF/CEILING STRUCTURES
    12 - 3.5.1 Openings in suspended ceilings
    12 - 3.5.2 Variations from prototype
    13 - SECTION 4 SMOKE CONTROL
    13 - 4.1 GENERAL
    13 - 4.2 SCOPE
    13 - 4.3 APPLICATION
    13 - 4.4 OBJECTIVES
    13 - 4.5 EXTERNAL OPENINGS FOR AIR INTAKE AND SMOKE SPILL
    13 - 4.5.1 Location of openings for air intake and outlets
    13 - 4.5.2 Discharge at various levels
    13 - 4.6 DIRECTION OF SPILL AIR FLOW UNDER SMOKE-CONTROL CONDITIONS
    13 - 4.7 LOCATION OF SMOKE-SPILL AIR INLETS
    13 - 4.8 HEAT EXCHANGE EQUIPMENT
    13 - 4.9 AIR-CONTROL DAMPERS
    13 - 4.9.1 General
    13 - 4.9.2 High-temperature operation
    13 - 4.10 NOISE
    13 - 4.11 FIRE-ISOLATED EXITS
    13 - 4.12 FIRE DOORS–PRESSURE DIFFERENTIALS
    13 - 4.13 SMOKE-SPILL FAN
    14 - 4.14 DUCTWORK IN SMOKE-SPILL SYSTEMS
    14 - 4.15 AUTOMATIC SMOKE DETECTORS
    14 - 4.15.1 Type
    14 - 4.15.2 Location
    14 - 4.15.3 Monitoring equipment
    14 - 4.15.4 Monitoring period
    14 - 4.15.5 Alarm zones
    14 - 4.15.6 Supply air smoke detector
    14 - 4.15.7 Installation
    14 - 4.16 ELECTRICAL INSTALLATION
    14 - 4.16.1 Equipment
    14 - 4.16.2 Wiring
    15 - 4.16.3 Isolation switches
    15 - 4.17 CONTROL AND INDICATION
    15 - 4.17.1 Fire fans control panel (FFCP)
    15 - 4.17.2 Controls
    15 - 4.17.3 Indicators
    15 - 4.17.4 Notices and labels
    15 - 4.18 OPERATING INSTRUCTIONS
    15 - 4.18.1 Instructions
    15 - 4.18.2 Diagram
    15 - 4.19 TESTING
    15 - 4.19.1 General
    15 - 4.19.2 Objective
    15 - 4.19.3 Component testing
    16 - 4.19.4 Measurement
    16 - 4.20 NOISE
    16 - 4.21 TEST SCHEDULE
    16 - 4.22 TEST RESULTS
    17 - SECTION 5 CENTRAL AIR-HANDLING SYSTEMS
    17 - 5.1 APPLICATION
    17 - 5.2 GENERAL
    17 - 5.3 FIRE ISOLATION
    17 - 5.3.1 Smoke-spill system
    17 - 5.3.2 Ducts within other compartments
    17 - 5.3.3 Smoke-spill shafts
    17 - 5.3.4 Entry of air into the smoke-spill system
    17 - 5.4 FIRE DAMPERS
    17 - 5.5 SUBDUCTS
    17 - 5.5.1 Manufacture
    17 - 5.5.2 Outlet projection
    17 - 5.5.3 Installation
    18 - 5.6 ALTERNATIVE DESIGN
    18 - 5.7 PURGING ARRANGEMENT
    18 - 5.7.1 General
    18 - 5.7.2 Smoke-spill fan
    18 - 5.7.3 Return air fan
    18 - 5.7.4 Supply air fan
    18 - 5.7.5 Air-control damper
    18 - 5.7.6 Fire damper
    18 - 5.7.7 Operation under fire conditions
    19 - 5.8 ZONE SMOKE CONTROL
    19 - 5.8.1 General
    19 - 5.8.2 Performance criteria
    19 - 5.8.3 Basic requirements
    19 - 5.8.4 Smoke-spill fan
    19 - 5.8.5 Supply air fan
    19 - 5.8.6 Air-control dampers
    19 - 5.8.7 Air relief and make-up
    19 - 5.8.8 Operation under fire conditions
    21 - SECTION 6 INDIVIDUAL AIR-HANDLING PLANTS-ZONE SMOKE CONTROL SYSTEM
    21 - 6.1 APPLICATION
    21 - 6.2 GENERAL
    21 - 6.3 ALTERNATIVE DESIGN
    21 - 6.4 PERFORMANCE CRITERIA
    21 - 6.5 COMPONENTS WITHIN OTHER COMPARTMENTS
    21 - 6.6 SMOKE-SPILL FANS
    21 - 6.7 RETURN AIR SPILL AIR FANS
    21 - 6.8 SPILL AIR RELIEF
    21 - 6.9 SUPPLY AIR FAN
    21 - 6.10 AIR-CONTROL DAMPERS
    21 - 6.11 AIR RELIEF AND MAKE-UP
    21 - 6.12 OPERATION IN THE EVENT OF FIRE
    21 - 6.13 INDIVIDUAL AIR-HANDLING PLANTS INCORPORATING COMMON OUTDOOR AIR AND COMMON SPILL AIR SHAFTS
    21 - 6.13.1 General
    22 - 6.13.2 Smoke-spill fan
    22 - 6.13.3 Supply air fan
    22 - 6.13.4 Fire isolation
    22 - 6.13.5 Fire dampers
    22 - 6.13.6 Subducts
    23 - SECTION 7 MISCELLANEOUS AIR-HANDLING SYSTEMS
    23 - 7.1 APPLICATION
    23 - 7.2 OBJECTIVES
    23 - 7.3 GENERAL
    23 - 7.4 EXHAUST SYSTEMS
    23 - 7.4.1 Minor exhaust systems
    23 - 7.4.2 Major exhaust systems
    23 - 7.5 KITCHEN HOOD EXHAUST SYSTEMS
    23 - 7.5.1 General
    23 - 7.5.2 Common exhaust
    23 - 7.5.3 Ductwork
    23 - 7.5.4 Plant isolation
    23 - 7.5.5 Fire dampers
    24 - 7.5.6 Operation under fire conditions
    24 - 7.6 CAR PARK VENTILATION SYSTEMS
    24 - 7.6.1 General
    24 - 7.6.2 Fire isolation
    24 - 7.6.3 Control
    24 - 7.6.4 Smoke detectors
    24 - 7.6.5 Operation
    24 - 7.7 SUPPLY AIR SYSTEMS
    24 - 7.7.1 Minor supply air systems
    24 - 7.7.2 Major supply air systems
    25 - SECTION 8 AIR PRESSURIZATION SYSTEMS FOR FIRE-ISOLATED EXITS
    25 - 8.1 GENERAL
    25 - 8.2 SCOPE
    25 - 8.3 OBJECTIVE
    25 - 8.4 DEEMED-TO-COMPLY SYSTEM
    25 - 8.4.1 General
    25 - 8.4.2 Performance criteria
    26 - 8.4.3 Air pressurization fans
    26 - 8.4.4 Pressure relief
    26 - 8.4.5 Automatic smoke detectors
    26 - 8.4.6 Electrical installation
    26 - 8.4.7 Control and indication
    26 - 8.4.8 Operation under fire conditions
    26 - 8.4.9 Testing
    26 - 8.5 ALTERNATIVE DESIGN
    27 - APPENDIX A - STAIR PRESSURIZATION COMMISSIONING TESTS
    27 - A1 GENERAL
    27 - A2 PROCEDURES
    27 - A3 PURGE SYSTEMS
    27 - A4 ZONE SYSTEMS
    27 - A5 RESTORATION TIME PERFORMANCE
    28 - A6 NOISE LEVEL MEASUREMENTS
    28 - A7 MEASUREMENT OF DOOR OPENING FORCE
    28 - A8 MEASUREMENT OF AIR VELOCITY THROUGH A DOORWAY
    28 - A8.1 Time average method
    28 - A8.2 Instantaneous readout average method
    30 - APPENDIX B - COMMENTARY TO SECTIONS 3 TO 8
    30 - SECTION 3 OPENINGS IN FIRE-RESISTING CONSTRUCTION
    31 - SECTION 4 SMOKE CONTROL
    31 - C4.2 SCOPE
    31 - C4.3 APPLICATION
    31 - C4.4 OBJECTIVES
    31 - C4.5 EXTERNAL OPENINGS FOR AIR INTAKE AND SMOKE SPILL
    31 - C4.5.1 Location of openings for air intake and outlets
    31 - C4.5.2 Discharge at various levels
    32 - C4.6 DIRECTION OF SPILL AIR FLOW UNDER SMOKE CONTROL CONDITIONS
    32 - C4.7 LOCATION OF SMOKE-SPILL AIR INLETS
    32 - C4.9 AIR-CONTROL DAMPERS
    32 - C4.10 NOISE
    32 - C4.11 FIRE-ISOLATED EXITS
    32 - C4.12 FIRE DOORS–PRESSURE DIFFERENTIALS
    32 - C4.13 SMOKE-SPILL FAN
    33 - C4.15 AUTOMATIC SMOKE DETECTORS
    33 - C4.15.1 Type
    33 - C4.15.2 Location
    33 - C4.15.4 Monitoring period
    33 - C4.15.5 Alarm zones
    33 - C4.15.6 Supply air smoke detector
    33 - C4.16 ELECTRICAL INSTALLATION
    33 - C4.16.1 Equipment
    33 - C4.16.2 Wiring
    33 - C4.17 CONTROL AND INDICATION
    33 - C4.18 OPERATING INSTRUCTIONS
    34 - C4.19 TESTING
    34 - C4.19.1 General
    35 - SECTION 5 CENTRAL AIR-HANDLING SYSTEMS
    35 - C5.3 FIRE ISOLATION
    35 - C5.3.1 Smoke-spill system
    35 - C5.3.2 Ducts within other compartments
    35 - C5.3.3 Smoke-spill shafts
    35 - C5.3.4 Entry of air into the smoke-spill system
    35 - C5.4 FIRE DAMPERS
    35 - C5.5 SUBDUCTS
    35 - C5.7 PURGING ARRANGEMENT
    36 - C5.7.2 Smoke-spill fans
    36 - C5.7.4 Supply air fan
    36 - C5.7.5 Air-control damper
    36 - C5.7.7 Operation under fire conditions
    36 - C5.8 ZONE SMOKE CONTROL
    36 - C5.8.2 Performance criteria
    37 - C5.8.4 Smoke-spill fan
    37 - C5.8.7 Air relief and make-up
    37 - C5.8.8 Operation under fire condi tions
    38 - SECTION 6 INDIVIDUAL AIR-HANDLING PLANTS-ZONE SMOKE CONTROL SYSTEMS
    38 - C6.4 PERFORMANCE CRITERIA
    38 - C6.5 COMPONENTS WITHIN OTHER COMPARTMENTS
    38 - C6.6 SMOKE-SPILL FANS
    38 - C6.8 SPILL AIR RELIEF
    38 - C6.9 SUPPLY AIR FAN
    38 - C6.10 AIR-CONTROL DAMPER
    38 - C6.11 AIR RELIEF AND MAKE-UP
    38 - C6.12 OPERATION IN THE EVENT OF FIRE
    38 - C6.13 INDIVIDUAL AIR-HANDLING PLANTS INCORPORATING COMMON OUTDOOR AIR AND COMMON SPILL AIR SHAFTS
    40 - SECTION 7 MISCELLANEOUS AIR-HANDLING SYSTEMS
    40 - C7.4 EXHAUST SYSTEMS
    40 - C7.5 KITCHEN HOOD EXHAUST SYSTEMS
    40 - C7.6 CAR PARK VENTILATION SYSTEMS
    40 - C7.7 SUPPLY AIR SYSTEMS
    41 - SECTION 8 AIR PRESSURIZATION SYSTEMS FOR FIRE-ISOLATED EXITS

    Abstract - (Show below) - (Hide below)

    Sets out the requirements for those aspects of design, construction, installation and operation of air-handling systems with a view to minimizing the spread of smoke and fire through buildings by way of the air-handling systems.

    Scope - (Show below) - (Hide below)

    This Section sets out the documents referred to in this Standard, and the definitions that shall apply to this document.

    General Product Information - (Show below) - (Hide below)

    Committee ME-062
    Document Type Standard
    Product Note See also AS/NZS 1668.1:1998
    Publisher Standards Australia
    Status Superseded
    Superseded By
    Supersedes

    History - (Show below) - (Hide below)

    Available SupersededUnder Revision See DR 96503 First published in part as AS 1668.1-1974.Second edition 1979.MP 47.C1 first published 1980.AS 1668.1-1979 and MP 47.C1-1980 revised and amalgamated as AS 1668.1-1991. First published in part as AS 1668.1-1974. Second edition 1979. MP 47.C1 first published 1980. AS 1668.1-1979 and MP 47.C1-1980 revised and amalgamated as AS 1668.1-1991.

    Standards Referenced By This Book - (Show below) - (Hide below)

    AS 1682.1-1990 Fire dampers Specification
    AS 1682.2-1990 Fire Dampers Installation
    AS 2484.1-1990 Fire - Glossary of terms Fire tests (Reconfirmed 2016)
    AS 2106-1980 Methods for the determination of the flashpoint of flammable liquids (closed cup)
    AS 1530.1-1994 Methods for fire tests on building materials, components and structures Combustibility test for materials (Reconfirmed 2016)
    AS 1670-1986 Automatic fire detection and alarm systems - System design, installation, and commissioning
    AS 1530.3-1989 Methods for fire tests on building materials, components and structures Simultaneous determination of ignitability, flame propagation, heat release and smoke release
    AS 3000-1986 Electrical installations - Buildings, structures and premises (known as the SAA Wiring Rules)
    AS 3013-1990 Electrical installations - Wiring systems for specific applications
    AS 1603.4-1987 Automatic fire detection and alarm systems - Control and indicating equipment
    AS 1530.4-1990 Methods for fire tests on building materials, components and structures Fire-resistance tests of elements of building construction
    AS 1668.2-1991 The use of mechanical ventilation and air-conditioning in buildings Mechanical ventilation for acceptable indoor-air quality
    AS 3102-1983 Approval and test specification for electric duct heaters
    AS 3772-1990 Fire protection of cooking areas

    Standards Referencing This Book - (Show below) - (Hide below)

    AS 4429(INT)-1996 Methods of test and rating requirements for smoke-spill fans
    AS 1324.1-1996 Air filters for use in general ventilation and airconditioning - Application, performance and construction
    AS/NZS 4391(INT):1996 Smoke management systems - Hot smoke test
    AS/NZS 2430.3.9:1997 Classification of hazardous areas - Examples of area classification - Miscellaneous
    AS 1670.1-1995 Fire detection, warning, control and intercom systems - System design, installation and commissioning Fire
    HB 37.4-1994 Handbook of Australian fire Standards Building materials, products and construction (Reconfirmed 2016)
    AS 1851.6-1997 Maintenance of fire protection equipment - Management procedures for maintaining the fire and smoke control features of air-handling systems
    AS 1530.4-1997 Methods for fire tests on building materials, components and structures Fire-resistance tests of elements of building construction
    AS 3533.1-1997 Amusement rides and devices - Design and construction
    AS 2118.1-1995 Automatic fire sprinkler systems - Standard
    AS 1603.13-1998 Automatic fire detection and alarm systems - Duct sampling units
    AS 2676.1-1992 Guide to the installation, maintenance, testing and replacement of secondary batteries in buildings - Vented cells
    AS/NZS 3013:1995 Electrical installations - Classification of the fire and mechanical performance of wiring systems
    AS 4254-1995 Ductwork for air-handling systems in buildings
    AS 1670.1-2004 Fire detection, warning, control and intercom systems - System design, installation and commissioning Fire
    • Access your standards online with a subscription

      Features

      • Simple online access to standards, technical information and regulations
      • Critical updates of standards and customisable alerts and notifications
      • Multi - user online standards collection: secure, flexibile and cost effective