BS EN 50577:2015
Current
The latest, up-to-date edition.
Electric cables. Fire resistance test for unprotected electric cables (P classification)
Hardcopy , PDF
English
31-12-2015
European foreword
Introduction
1 Scope
2 Normative references
3 Terms and definitions
4 Test equipment
5 Test conditions
6 Test specimen
7 Test procedure
8 Duration of survival
9 Test report
Annex A (normative) - Field of direct application
Annex B (normative) - Extended application of test results
Bibliography
Defines a test method to evaluate the maintenance of circuit integrity of electric cables which have intrinsic resistance to fire under fire conditions, in order to classify the electric cable according to EN 13501-3.
Committee |
GEL/20/18
|
DevelopmentNote |
Supersedes 12/30260450 DC. (01/2016)
|
DocumentType |
Standard
|
Pages |
32
|
PublisherName |
British Standards Institution
|
Status |
Current
|
Supersedes |
This European Standard specifies a test method to evaluate the maintenance of circuit integrity of electric cables which have intrinsic resistance to fire under fire conditions, in order to classify the electric cable according to EN13501‑3 . The test determines the survival time for circuit integrity of the electric cable when exposed to fire under the conditions of the EN1363‑1 standard time/temperature curve. This European Standard is used in conjunction with EN1363‑1 . This European Standard applies to electric power and control cables with rated voltage up to and including 600/1000V. The cable is tested in a standardized representative installation condition. The test does not assess the performance of the cable management system. NOTE Optical fibre cables and copper communication cables could be tested using this test method, however verification procedures for such cables were still under development when this document has been circulated for vote (2015-07-24). This European Standard includes field of direct application ( AnnexA) and rules for extended application of test results (EXAP) ( AnnexB). The selection of cables to be tested for classification of a family is given in AnnexB. In case the selection of the cables does not comply with AnnexB, the test results are only applicable to the tested cables.
Standards | Relationship |
EN 50577:2015 | Identical |
IEC 61537:2006 | Cable management - Cable tray systems and cable ladder systems |
IEC 60228:2004 | Conductors of insulated cables |
EN 50200:2015 | Method of test for resistance to fire of unprotected small cables for use in emergency circuits |
ISO 13943:2017 | Fire safety — Vocabulary |
EN 60228:2005 COR 2005 | CONDUCTORS OF INSULATED CABLES |
IEC 60269-3:2010+AMD1:2013 CSV | Low-voltage fuses - Part 3: Supplementary requirements for fuses foruse by unskilled persons (fuses mainly for household or similar applications) - Examples of standardized systems of fuses A to F |
PREN 1366-11 : DRAFT 2014 | FIRE RESISTANCE TESTS FOR SERVICE INSTALLATIONS - PART 11: FIRE PROTECTIVE SYSTEMS FOR CABLE SYSTEMS AND ASSOCIATED COMPONENTS |
EN 13501-3:2005+A1:2009 | Fire classification of construction products and building elements - Part 3: Classification using data from fire resistance tests on products and elements used in building service installations: fire resisting ducts and fire dampers |
EN ISO 13943:2017 | Fire safety - Vocabulary (ISO 13943:2017) |
EN 1363-1:2012 | Fire resistance tests - Part 1: General Requirements |
EN 61537:2007 | Cable management - Cable tray systems and cable ladder systems |
Access your standards online with a subscription