ASTM D 5837 : 2015 : REDLINE
Current
The latest, up-to-date edition.
Standard Test Method for Furanic Compounds in Electrical Insulating Liquids by High-Performance Liquid Chromatography (HPLC)
English
20-10-2015
CONTAINED IN VOL. 10.03, 2015 Outlines the determination in electrical insulating liquids of products of degradation of cellulosic materials, e.g. pressboard, cotton materials and paper, usually found as insulating materials in electrical equipment.
Committee |
D 27
|
DocumentType |
Redline
|
Pages |
9
|
PublisherName |
American Society for Testing and Materials
|
Status |
Current
|
1.1This test method covers the determination in electrical insulating liquids of products of the degradation of cellulosic materials such as paper, pressboard, and cotton materials typically found as insulating materials in electrical equipment. These degradation products are substituted furan derivatives, commonly referred to as furanic compounds or furans. This test method allows either liquid/liquid or solid phase extraction (SPE) of the furanic compounds from the sample matrix followed by analysis for specific furanic compounds by HPLC or direct injection for analysis of specific furanic compounds by HPLC.
1.2The individual furanic compounds that may be identified and quantified include the following:
5-hydroxymethyl-2-furaldehyde |
furfuryl alcohol |
2-furaldehyde |
2-acetylfuran |
5-methyl-2-furaldehyde |
1.3The direct injection method generally has a higher limit of detection, especially for furfuryl alcohol. Greater interference for furfuryl alcohol may be expected when using the direct injection method as opposed to extraction methods.
1.4This test method has been used to successfully test for furanic compounds in mineral insulating oil, silicone fluid, high fire point electrical insulating oils of mineral origin, askarels, and perchloroethylene-based dielectric fluids.
1.5The values stated in SI units are to be regarded as standard. No other units of measurement are included in this standard.
1.6This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.
ASTM D 5282 : 2005 | Standard Test Methods for Compatibility of Construction Material with Silicone Fluid Used for Electrical Insulation |
IEEE DRAFT C57.93 : D13 2005 | INSTALLATION AND MAINTENANCE OF LIQUID-IMMERSED POWER TRANSFORMERS |
IEEE C57.106-2006 | IEEE Guide for Acceptance and Maintenance of Insulating Oil in Equipment |
CAN/CSA-C50-14 (R2018) | Mineral insulating oil, electrical, for transformers and switches |
IEEE C57.152-2013 | IEEE Guide for Diagnostic Field Testing of Fluid-Filled Power Transformers, Regulators, and Reactors |
IEEE C57.93-2007 | IEEE Guide for Installation and Maintenance of Liquid-Immersed Power Transformers |
IEEE C57.147-2008 | IEEE Guide for Acceptance and Maintenance of Natural Ester Fluids in Transformers |
ASTM D 5282 : 2005 : R2012 | Standard Test Methods for Compatibility of Construction Material with Silicone Fluid Used for Electrical Insulation |
ASTM D 923 : 2015 : REDLINE | Standard Practices for Sampling Electrical Insulating Liquids |
IEC 61198:1993 | Mineral insulating oils - Methods for the determination of 2-furfural and related compounds |