1 Scope
2 Normative references
3 Terms and definitions
4 General purpose cables
Annex A (normative) - Tests for cables to EN 50525-3-31
Annex B (normative) - General data
Bibliography

Pertains to non-sheathed single core cables insulated with halogen-free thermoplastic compound and having low emission of smoke and corrosive gases when exposed to fire.

Committee
GEL/20/17
DevelopmentNote
To be read in conjunction with BS EN 50525-1. Supersedes 08/30188839 DC. (10/2011)
DocumentType
Standard
Pages
18
PublisherName
British Standards Institution
Status
Current
Supersedes

EN 50525-3-31 applies to non-sheathed single core cables insulated with halogen-free thermoplastic compound and having low emission of smoke and corrosive gases when exposed to fire.

NOTE 1 Low emission of smoke is checked in accordance with EN 61034-2. Low emission of corrosive gases is checked as part of the check for absence of halogens (see Annex B of EN 50525-1).

The cables are of rated voltages U0/U up to and including 450/750 V.

NOTE 2 Cables rated 450/750 V may be used at 600/1 000 V when this cable is used in fixed installations with mechanical protection, within switchgear and control gear - see HD 516.

For cables rated at 450/750 V there are two types, Type 1 and Type 2. Type 2 cables are required to meet a more severe test for resistance to flame propagation (EN 60332-3-24) than Type 1, and have particular suitability for installation in bunches (see also HD 516).

The cables are intended for fixed wiring applications.

The maximum conductor operating temperature for each of the cables in this standard is 70 °C.

NOTE 3 HD 516 contains extensive guidance on the safe use of cables in this standard.

This EN 50525-3-31 should be read in conjunction with EN 50525-1, which specifies general requirements.

Standards Relationship
EN 50525-3-31:2011 Identical

EN 60719:1993 Calculation of the lower and upper limits for the average outer dimensions of cables with circular copper conductors and of rated voltages up to and including 450/750 V
IEC 60228:2004 Conductors of insulated cables
EN 60228:2005 COR 2005 CONDUCTORS OF INSULATED CABLES
EN 60332-1-2:2004/A11:2016 TESTS ON ELECTRIC AND OPTICAL FIBRE CABLES UNDER FIRE CONDITIONS - PART 1-2: TEST FOR VERTICAL FLAME PROPAGATION FOR A SINGLE INSULATED WIRE OR CABLE - PROCEDURE FOR 1 KW PRE-MIXED FLAME (IEC 60332-1-2:2004/A1:2015)
IEC 60332-3-24:2000+AMD1:2008 CSV Tests on electric and optical fibre cables under fire conditions - Part 3-24: Test for vertical flame spread of vertically-mounted bunched wires or cables - Category C
IEC 60332-1-2:2004+AMD1:2015 CSV Tests on electric and optical fibre cables under fire conditions - Part 1-2: Test for vertical flame propagation for a single insulatedwire or cable - Procedure for 1 kW pre-mixed flame
IEC 60719:1992 Calculation of the lower and upper limits for the average outer dimensions of cables with circular copper conductors and of rated voltages up to and including 450/750 V
EN 50525-1:2011 Electric cables - Low voltage energy cables of rated voltages up to and including 450/750 V (U0/U) - Part 1: General requirements
EN 61034-2:2005/A1:2013 MEASUREMENT OF SMOKE DENSITY OF CABLES BURNING UNDER DEFINED CONDITIONS - PART 2: TEST PROCEDURE AND REQUIREMENTS (IEC 61034-2:2005/A1:2013)
HD 516 S2:1997/A2:2008 GUIDE TO USE OF LOW VOLTAGE HARMONIZED CABLES
EN 50395 : 2005 AMD 1 2011 ELECTRICAL TEST METHODS FOR LOW VOLTAGE ENERGY CABLES
EN 60332-3-24:2009 TESTS ON ELECTRIC AND OPTICAL FIBRE CABLES UNDER FIRE CONDITIONS - PART 3-24: TEST FOR VERTICAL FLAME SPREAD OF VERTICALLY-MOUNTED BUNCHED WIRES OR CABLES - CATEGORY C
IEC 60811-1-4:1985 Common test methods for insulating and sheathing materials of electric cables - Part 1: Methods for general application - Section Four: Tests at low temperature
IEC 61034-2:2005+AMD1:2013 CSV Measurement of smoke density of cables burning under definedconditions - Part 2: Test procedure and requirements
EN 50396 : 2005 AMD 1 2011 NON ELECTRICAL TEST METHODS FOR LOW VOLTAGE ENERGY CABLES
EN 50363-7:2005 Insulating, sheathing and covering materials for low voltage energy cables - Part 7: Halogen-free, thermoplastic insulating compounds
EN 60811-1-4:1995/A2:2001 INSULATING AND SHEATHING MATERIALS OF ELECTRIC CABLES - COMMON TEST METHODS - PART 1-4: GENERAL APPLICATION - TESTS AT LOW TEMPERATURE