BS EN 50532:2010
Superseded
A superseded Standard is one, which is fully replaced by another Standard, which is a new edition of the same Standard.
View Superseded by
Compact equipment assembly for distribution substations (CEADS)
Hardcopy , PDF
31-01-2017
English
31-05-2010
Committee |
PEL/17
|
DevelopmentNote |
Supersedes 09/30202403 DC. (06/2010)
|
DocumentType |
Standard
|
Pages |
66
|
PublisherName |
British Standards Institution
|
Status |
Superseded
|
SupersededBy | |
Supersedes |
This European Standard specifies the service conditions, rated characteristics, general structural requirements and test methods of the prefabricated assembly of the main electrical functional units of a HV/LV Distribution Substation, duly interconnected, for alternating current of rated operating voltages above 1 kV and up to and including 52 kV on the HV side, service frequency 50 Hz. This assembly is to be cable-connected to the network.
This Compact Equipment Assembly for Distribution Substation (CEADS) as defined in this standard is designed and tested to be a single product with a single serial number and one set of documentation. Such equipment is delivered as single transport unit. For practical reasons manufacturer and user can agree to transport the unit dismantled if transport or installation of the complete CEADS is not possible. In that case suitable verification tests shall be carried out at the installation site.
Note 1: Where the functional units are independent each functional unit will also have its own serial number.
A CEADS is not a Distribution Substation, either prefabricated (covered by EN 62271-202) or not (covered by EN 61936-1). However CEADS is intended to become part of a Distribution Substation assembling the HV equipment, the power transformer and the LV equipment duly interconnected (see Annex C, which also explains the origin and types of CEADS).
The functions of a CEADS are:
switching and control for the operation of the HV side and protection of the HV/LV transformer functional unit;
HV/LV transformation;
switching and control for the operation and protection of the LV feeders.
However relevant provisions of this standard are also applicable to designs where not all of these functions exist (e.g. equipment comprising only HV/LV transformation and switching and control for the operation and protection of the LV feeder functions).
For public distribution networks, CEADS are intended for installation within an indoor or outdoor closed electrical operating area (see Definition 1.3.3) forming part of a Distribution Substation.
For industrial applications, such as factories, installation of CEADS outside a closed electrical operating area may be allowed provided that safety regulations are fulfilled by additional measures adopted at the installation site under the responsibility of the designer of the installation.
This standard considers the potential interaction between the individual functions when closely installed and interconnected to form a type tested assembly and defines ratings, particular design and construction requirements and test procedures for this assembly.
NOTE 2 Interaction is the influence of one functional units of the equipment on another (i.e. electrical mechanical and thermal stresses).
NOTE 3 For the purpose of this standard a self-protected transformer is considered not as a CEADS, but as a functional unit, designed and type tested to its own product standard EN 60076-13.
Standards | Relationship |
EN 50532:2010 | Identical |
IEC 60243-1:2013 | Electric strength of insulating materials - Test methods - Part 1: Tests at power frequencies |
EN 62262:2002 | Degrees of protection provided by enclosures for electrical equipment against external mechanical impacts (IK code) |
IEC 60721-1:1990+AMD1:1992+AMD2:1995 CSV | Classification of environmental conditions - Part 1: Environmental parameters and their severities |
IEC 61936-1:2010+AMD1:2014 CSV | Power installations exceeding 1 kV a.c. - Part 1: Common rules |
EN 60068-2-75:2014 | Environmental testing - Part 2-75: Tests - Test Eh: Hammer tests |
IEC 62271-200:2011 | High-voltage switchgear and controlgear - Part 200: AC metal-enclosed switchgear and controlgear for rated voltages above 1 kV and up to and including 52 kV |
IEC 62271-202:2014 | High-voltage switchgear and controlgear - Part 202: High-voltage/ low-voltage prefabricated substation |
IEC 62271-201:2014 | High-voltage switchgear and controlgear - Part 201: AC solid-insulation enclosed switchgear and controlgear for rated voltages above 1 kV and up to and including 52 kV |
EN 62271-1:2017 | High-voltage switchgear and controlgear - Part 1: Common specifications for alternating current switchgear and controlgear |
IEC 60364-4-41:2005+AMD1:2017 CSV | Low voltage electrical installations - Part 4-41: Protection for safety - Protection against electric shock |
IEC 60050-441:1984 | International Electrotechnical Vocabulary (IEV) - Part 441: Switchgear, controlgear and fuses |
EN 60076-5:2006 | Power transformers - Part 5: Ability to withstand short-circuit |
EN 62271-201:2014 | High-voltage switchgear and controlgear - Part 201: AC solid-insulation enclosed switchgear and controlgear for rated voltages above 1 kV and up to and including 52 kV |
EN 60076-13 : 2006 | POWER TRANSFORMERS - PART 13: SELF-PROTECTED LIQUID-FILLED TRANSFORMERS |
HD 60364-4-41:2017/A11:2017 | LOW-VOLTAGE ELECTRICAL INSTALLATIONS - PART 4-41: PROTECTION FOR SAFETY - PROTECTION AGAINST ELECTRIC SHOCK |
IEC 60076-10:2016 | Power transformers - Part 10: Determination of sound levels |
EN 60076-11:2004 | Power transformers - Part 11: Dry-type transformers |
IEC 60076-5:2006 | Power transformers - Part 5: Ability to withstand short circuit |
HD 637 S1:1999/corrigendum:2005 | POWER INSTALLATIONS EXCEEDING 1 KV A.C. |
EN 62271-202:2014/AC:2014 | HIGH-VOLTAGE SWITCHGEAR AND CONTROLGEAR - PART 202: HIGH-VOLTAGE/LOW-VOLTAGE PREFABRICATED SUBSTATION (IEC 62271-202:2014) |
IEC TR 62271-300:2006 | High-voltage switchgear and controlgear - Part 300: Seismic qualification of alternating current circuit-breakers |
EN 50464-4 : 2007 AMD 1 2011 | THREE-PHASE OIL-IMMERSED DISTRIBUTION TRANSFORMERS 50 HZ, FROM 50 KVA TO 2500 KVA WITH HIGHEST VOLTAGE FOR EQUIPMENT NOT EXCEEDING 36 KV - PART 4: REQUIREMENTS AND TESTS CONCERNING PRESSURISED CORRUGATED TANKS |
EN 60947-1:2007/A2:2014 | LOW-VOLTAGE SWITCHGEAR AND CONTROLGEAR - PART 1: GENERAL RULES (IEC 60947-1:2007/A2:2014) |
EN 50464-1 : 2007 AMD 1 2012 | THREE-PHASE OIL-IMMERSED DISTRIBUTION TRANSFORMERS 50 HZ, FROM 50 KVA TO 2500 KVA WITH HIGHEST VOLTAGE FOR EQUIPMENT NOT EXCEEDING 36 KV - PART 1: GENERAL REQUIREMENTS |
EN 61936-1 : 2010 AMD 1 2014 | POWER INSTALLATIONS EXCEEDING 1 KV A.C. - PART 1: COMMON RULES (IEC 61936-1:2010/A1:2014) |
EN 60076-10:2016 | Power transformers - Part 10: Determination of sound levels |
IEC 60721-2-2:2012 | Classification of environmental conditions - Part 2-2: Environmental conditions appearing in nature - Precipitation and wind |
ISO/IEC Guide 51:2014 | Safety aspects — Guidelines for their inclusion in standards |
IEC 60529:1989+AMD1:1999+AMD2:2013 CSV | Degrees of protection provided by enclosures (IP Code) |
IEC 60076-1:2011 | Power transformers - Part 1: General |
IEC 60947-1:2007+AMD1:2010+AMD2:2014 CSV | Low-voltage switchgear and controlgear - Part 1: General rules |
EN 60664-1:2007 | Insulation coordination for equipment within low-voltage systems - Part 1: Principles, requirements and tests |
IEC 60439-1:1999+AMD1:2004 CSV | Low-voltage switchgear and controlgear assemblies - Part 1: Type-tested and partially type-tested assemblies |
IEC 62262:2002 | Degrees of protection provided by enclosures for electrical equipment against external mechanical impacts (IK code) |
EN 60076-1:2011 | POWER TRANSFORMERS - PART 1: GENERAL (IEC 60076-1:2011) |
EN 60243-1:2013 | ELECTRIC STRENGTH OF INSULATING MATERIALS - TEST METHODS - PART 1: TESTS AT POWER FREQUENCIES (IEC 60243-1:2013) |
IEC 62271-1:2017 | High-voltage switchgear and controlgear - Part 1: Common specifications for alternating current switchgear and controlgear |
IEC 60076-2:2011 | Power transformers - Part 2: Temperature rise for liquid-immersed transformers |
IEC 60068-2-75:2014 | Environmental testing - Part 2-75: Tests - Test Eh: Hammer tests |
IEC 60721-2-4:1987+AMD1:1988 CSV | Classification of environmental conditions - Part 2-4: Environmental conditions appearing in nature - Solar radiation and temperature |
EN 60721-1:1995/A2:1995 | CLASSIFICATION OF ENVIRONMENTAL CONDITIONS - PART 1: ENVIRONMENTAL PARAMETERS AND THEIR SEVERITIES |
IEC 60076-13:2006 | Power transformers - Part 13: Self-protected liquid-filled transformers |
EN 60529:1991/AC:2016-12 | DEGREES OF PROTECTION PROVIDED BY ENCLOSURES (IP CODE) (IEC 60529 EDITION 2.2 CORRIGENDUM 2:2015) |
EN 60076-2:2011 | Power transformers - Part 2: Temperature rise for liquid-immersed transformers |
IEC 60664-1:2007 | Insulation coordination for equipment within low-voltage systems - Part 1: Principles, requirements and tests |
EN 62271-200:2012/AC:2015 | HIGH-VOLTAGE SWITCHGEAR AND CONTROLGEAR - PART 200: AC METAL-ENCLOSED SWITCHGEAR AND CONTROLGEAR FOR RATED VOLTAGES ABOVE 1 KV AND UP TO AND INCLUDING 52 KV (IEC 62271-200:2011) |
Access your standards online with a subscription
Features
-
Simple online access to standards, technical information and regulations.
-
Critical updates of standards and customisable alerts and notifications.
-
Multi-user online standards collection: secure, flexible and cost effective.